Home decoration harness safety load flow comparison table

Household Wiring Safe Current-Carrying Capacity Reference Table

Ⅰ. Household Wiring Safe Current-Carrying Capacity Reference Table

Wire Cross-Sectional Area (mm²)Open Wiring (A)Conduit Wiring (A)Concealed Wiring (A)Recommended ApplicationsSuggested Circuit Breaker (A)
1.015108Lighting, Signal Lines10A (Type C)
1.5181210General Sockets, Lighting16A (Type C)
2.5251614Wall-Mounted AC, Kitchen Appliances20A (Type C)
4.0322520Cabinet AC, High-Power Appliances25A (Type C)
6.0403226Central AC, Main Inlet Line32A (Type C)
10.0554235Main Distribution Box, High-Current Equipment40A (Type C)
  • Open Wiring (e.g., cable trays, bridges): Best heat dissipation, highest current-carrying capacity.
  • Conduit Wiring (PVC or metal conduits): Poorer heat dissipation, current-carrying capacity reduced by ~20%.
  • Concealed Wiring (embedded in walls or floors): Worst heat dissipation, current-carrying capacity further reduced by 10%~15%.
  • Standard current-carrying capacity is based on 30°C ambient temperature. If the temperature is higher (e.g., 40°C), derate by 5%~10%.
  • Type C circuit breakers are recommended for general household use, while Type D (high inrush current-resistant) is suitable for motorized equipment.
  • The rated current of the circuit breaker should be ≤ the wire’s safe current-carrying capacity. For example, 2.5mm² conduit wiring (16A) should be paired with a 16A or 20A breaker.
  • Aluminum wires have lower current-carrying capacity and are prone to oxidation. Copper core wires are strongly recommended for household wiring.

II. Key Factors Affecting Current-Carrying Capacity

Wiring MethodHeat Dissipation ConditionCurrent-Carrying Capacity Adjustment FactorTypical Scenarios
Open WiringExposed to air, best heat dissipation1.0 (baseline)Cable trays, bridges, open wiring
Conduit WiringWires in PVC or metal conduits, limited heat dissipation0.8 (20% reduction)Concealed household wiring
Concealed WiringWires buried in walls or floors, poorest heat dissipation0.7 (30% reduction)Wall or floor hidden projects
Ambient Temperature (°C)Current-Carrying Capacity Adjustment FactorImpact Description
30°C (standard)1.0Baseline, no adjustment needed
40°C0.9High-temperature environments (e.g., rooftops, direct sunlight areas)
50°C0.8Extreme high temperatures (e.g., boiler rooms, tropical regions)
Conductor MaterialConductivityCurrent-Carrying Capacity Comparison (Same Cross-Sectional Area)Suitability for Household Use
Copper Wire (BV)100%Baseline (e.g., 2.5mm² = 25A)Recommended, safe and reliable
Aluminum Wire (BLV)61%~60% of copper wire capacity (requires larger gauge)Not recommended, prone to oxidation and overheating
Insulation MaterialTemperature Resistance RatingLong-Term Allowable TemperatureCurrent-Carrying Capacity Comparison (Relative to PVC)
PVC (Polyvinyl Chloride)70℃70℃Baseline (e.g., 2.5mm² conduit wiring = 16A)
XLPE (Cross-Linked Polyethylene)90℃90℃15%~20% higher (more heat-resistant)

I: Current (A) R: Wire resistance (Ω/m, ~0.018Ω/mm²·m for copper wires) L: Wire length (m)

III. Household Circuit Design Recommendations

Circuit TypeRecommended Wire Gauge (mm²)Circuit Breaker (A)Application Scenario
Lighting Circuit1.510Whole-house lighting system
General Socket Circuit2.516Living room/bedroom sockets
Kitchen Circuit4.025Rice cookers, microwaves etc.
Bathroom Circuit4.025Water heaters, bath heaters
AC Circuit4.0/6.025/32Wall-mounted/cabinet AC
High-power Circuit6.032Instant water heaters, induction cooktops
Main Incoming Circuit10.040-63Main distribution box switch
  • Type C: For general household appliances (lighting, sockets)
  • Type D: For motorized equipment (AC, refrigerators)
Wire Gauge (mm²)Max Current (A)Recommended Breaker (A)Protection Type
1.51210Type C
2.51616Type C+RCD
4.02525Type C/D+RCD
6.03232Type D+RCD
  • 3HP AC rated current ~10A, startup current ~30A
  • Use 4mm² wire (25A capacity)
  • Match with 25A Type D breaker (handles inrush current)
  • Recommend 2-3 independent circuits
  • Use moisture-resistant sockets
  • Dedicated circuit for high-power appliances
  • RCD protection mandatory
  • Dedicated circuit for water heaters
  • Separate circuit for bath heaters
  • Dedicated circuit for AC units
  • Multiple sockets for TV console
  • Proper height for bedside sockets
Post-installation checks:

IV. Frequently Asked Questions

  • Minimum: 2.5mm² copper wire (16A in conduit)
  • Optimal: 4.0mm² copper wire (25A in conduit)
  • Paired with a 20A Type C or D circuit breaker
  • Main line: 6.0mm² copper wire
  • Sub-circuits:
    • High-power appliances (ovens, etc.): 4.0mm² dedicated circuit
    • General appliances: 2.5mm² circuit
    • Lighting: 1.5mm² circuit
  • Main switch recommendation: 40A with RCD
  1. Conduit current-carrying capacity: 2.5mm² in conduit = 16A
  2. Long-term safety: At 80% load rate, continuous current should be ≤12.8A
  3. Protection matching: A 16A breaker trips promptly during overload
  • Wire heating is gradual and may not be immediately apparent
  • Overload accelerates insulation aging, creating fire hazards
  • Breakers must strictly match the wire’s current-carrying capacity
  1. Assess current condition:
    • Check wire gauge (typically 2.5mm² for old aluminum wires)
    • Test insulation condition
  2. Upgrade options:
    • Complete replacement with copper wires (recommended)
    • Minimum requirement: High-power circuits must use copper
  3. Temporary solution:
    • Use copper-aluminum transition terminals
    • Never connect directly by twisting
  1. Increase wire gauge:
    • ≤50m: Standard sizing
    • 50-100m: Increase one gauge size
    • 100m: Increase two gauge sizes
  2. Use three-phase power:
    • Recommended for loads >8kW
    • Balance loads across phases
  1. Visual inspection:
    • Undamaged conduits
    • Secure junction boxes
  2. Electrical tests:
    • Insulation resistance ≥0.5MΩ
    • Ground resistance ≤4Ω
  3. Load test:
    • Operate under load for 1 hour
    • Check connection point temperatures
Conduit Diameter (mm)Max Wires (2.5mm²)Derating Factor
1630.7
2050.6
2570.5
  • Important circuits should use separate conduits
  • No more than 3 wires per conduit
  • Adjust current-carrying capacity per derating factor
  1. Identify trip type:
    • RCD trip: Circuit or appliance leakage
    • Overload trip: Excessive power consumption
  2. Solutions:
    • Restore power circuit-by-circuit to identify issue
    • Measure actual current in each circuit
    • Check appliance insulation
  • PVC-insulated wires: 15-20 years
  • XLPE-insulated wires: 20-30 years
    Replacement indicators:

Leave a Comment

Votre adresse e-mail ne sera pas publiée. Les champs obligatoires sont indiqués avec *

Aucun commentaire à afficher.

fr_FR

Ask For A Quick Quote

Contact Kabolux(sales@kabolux.com) to get a free quote and expert advice on custom cable assembly. Our team will provide the right solution for your project.

Please enable JavaScript in your browser to complete this form.
Enter your full name here
Example: user@website.com
Feel free to ask a question or simply leave a comment